| Low-voltage sensors and control circuits | 24 V DC | Usually low current; check device load and voltage drop over the cable run. | 2-core or multi-core copper control cable; 0.5–1.0 mm² conductors are common starting points. | Check polarity, conductor resistance, cable length, temperature rating, and separation from power wiring. |
| Analog instrumentation, such as 4–20 mA loops | Typically 24 V DC loop supply | Low-level analog signal; confirm loop resistance and transmitter requirements. | Twisted-pair, shielded instrumentation cable; commonly 0.5–0.75 mm² conductors. | Ground the shield according to the system design; consider electrical noise, route length, and hazardous-area requirements. |
| Industrial data communications | Signal-level circuits; follow the interface specification | Data rate, impedance, and maximum segment length depend on the protocol. | Use cable designed for the selected interface, such as a 100 Ω balanced-pair cable for many Ethernet applications. | Verify impedance, bandwidth, shielding, connector type, bend radius, and the applicable network standard. |
| Small three-phase motor supply | Commonly 400 V AC line-to-line in many IEC installations | A 7.5 kW motor may draw roughly 14–16 A at rated load; check the motor nameplate. | Four- or five-core copper power cable; 2.5 mm² may be a preliminary size for some installations, not a final selection. | Calculate ampacity, starting current, voltage drop, protective-device coordination, installation method, and earthing needs. |
| Medium-size three-phase motor supply | Commonly 400 V AC line-to-line in many IEC installations | A 22 kW motor may draw roughly 40–45 A at rated load; actual current depends on nameplate data and operating conditions. | Multi-core copper power cable; conductor size must be calculated for the actual installation. | Account for ambient temperature, grouping, tray or conduit installation, cable length, motor starting, and local electrical rules. |
| Variable-frequency drive (VFD) to motor | Selected to match the drive and motor, often 400 V AC systems | Size using the drive output and motor current ratings. | VFD-rated shielded motor cable with suitable insulation and symmetrical grounding conductors where required. | Check drive manufacturer guidance, cable length, EMC practices, shield termination, and motor insulation compatibility. |
| Outdoor or harsh-environment installation | Determine from the connected equipment and system design | Determine from the load or signal circuit; environmental conditions may affect cable selection. | Cable with suitable jacket, moisture resistance, UV resistance, and mechanical protection for the site. | Check chemical exposure, oil, abrasion, temperature range, water ingress, burial requirements, and fire performance. |