Electrical insulation film is often selected by thermal class, but the number needs context. IEC 60085 classifies insulation systems by thermal endurance, with classes including 155, 180, and 200°C.
A film’s stated class depends on its qualification in the intended system. Not a guarantee.
A 155°C class may fit moderate-temperature designs, while 180°C or 200°C classes can provide more thermal headroom in motors, transformers, and coils. Actual service life also depends on film thickness, winding pressure, moisture, voltage stress, and nearby materials.
A hot spot next to a copper conductor may age insulation faster than a surface reading suggests. The class alone does not specify dielectric strength or flexibility.
Check the test data for the exact film grade, then compare the expected hot-spot temperature with the system’s thermal class. Leave room for load cycles and manufacturing variation.
That margin can be difficult to estimate. Prototype temperature tests are useful, especially when airflow or enclosure geometry changes.