| 1 | Applicable product standard | Confirm that the PV-side SPD is designed and tested to the applicable edition of IEC 61643-31. AC-side protection is covered by a separate product standard, IEC 61643-11. | Test reports and certificates identifying the exact product model and standard edition. | Check that the documentation applies to the offered model, not merely a similar product family. |
| 2 | Maximum PV system voltage (UCPV) | The SPD’s maximum continuous operating voltage must be suitable for the PV array’s maximum open-circuit voltage, including the minimum design temperature correction required by the project. | Datasheet showing UCPV and the manufacturer’s application instructions. | Verify the rating against the module string voltage calculation and inverter input limits. |
| 3 | SPD type and lightning protection design | Select the SPD type to match the installation’s lightning protection and surge exposure assessment. Type 1, Type 2, and combined Type 1+2 devices serve different test and application needs. | Type designation, test classification, and installation guidance referencing the project’s protection design. | Have the project designer determine the required type; do not choose by type label alone. |
| 4 | Discharge-current ratings | Compare the declared impulse current (Iimp) where applicable, nominal discharge current (In), and maximum discharge current (Imax) using the specified test waveforms and ratings. | Datasheet and test report stating each rating, waveform, and test configuration. | Compare like-for-like ratings; values with different waveforms or test conditions are not directly interchangeable. |
| 5 | Voltage protection level (Up) | Check the declared protection level against the withstand voltage of the equipment being protected and the system design. | Datasheet specifying Up and the associated test conditions. | Confirm coordination with the inverter and other protected equipment; do not assess Up in isolation. |
| 6 | PV circuit configuration and poles | Check compatibility with the array grounding arrangement, positive and negative conductors, and the protection scheme required by the system design. | Wiring diagrams, pole configuration, and installation instructions for the exact model. | Ensure the wiring diagram matches the project topology and applicable local electrical rules. |
| 7 | Disconnect status and replacement | Review the device’s disconnection mechanism, status indication, and whether replaceable protection modules are available. | Product drawings, indicator instructions, and module replacement procedure. | Plan inspection and replacement access, particularly for installations where downtime is costly. |
| 8 | Environmental and enclosure suitability | Compare the declared operating temperature, humidity limits, enclosure protection rating, and installation conditions with the actual site environment. | Datasheet, environmental test information, and enclosure or mounting details. | Check exposure to heat, moisture, dust, and outdoor conditions at the intended mounting location. |
| 9 | Quality control and traceability | Assess whether the manufacturer can identify production batches and provide documented inspection and testing controls. | Quality-system documentation, sample inspection records, and batch or serial-number traceability details. | Confirm the supplied goods can be traced to production records and matching technical documents. |
| 10 | Warranty, support, and delivery capability | Compare written warranty terms, technical response arrangements, spare-module availability, lead-time commitments, and export documentation support. | Warranty conditions, support contacts, stated lead times, and sample shipping documents. | Evaluate total project risk and lifecycle support, not just unit price. |