| Assembly design and verification | Design verification evidence for the complete low-voltage assembly, including temperature rise, dielectric properties, and short-circuit withstand where applicable. | IEC 61439-1: general rules; IEC 61439-2: power switchgear and controlgear assemblies. | IEC 61439-1 is used together with the relevant product part; it is not intended to be used alone. |
| Rated voltage and frequency | Declared rated operational voltage, rated insulation voltage, rated frequency, and system configuration. | IEC 61439-1 and IEC 61439-2; project electrical specifications. | The IEC 61439-2 scope covers assemblies for systems up to 1,000 V AC or 1,500 V DC. These are scope limits, not a product’s guaranteed rating. |
| Current and temperature rise | Rated current of the assembly and circuits, busbar ratings, loading assumptions, and temperature-rise verification. | IEC 61439-1 and IEC 61439-2. | Compare the declared ratings with the site load, ambient conditions, enclosure arrangement, and specified diversity assumptions. |
| Short-circuit performance | Rated short-time withstand current, conditional short-circuit rating where applicable, protective-device coordination, and the stated duration. | IEC 61439-1 and IEC 61439-2; applicable local electrical codes. | Request ratings and supporting verification for the proposed assembly configuration, not just for individual components. |
| Enclosure protection | Declared IP code for the assembled cabinet and the conditions under which it applies, including doors, covers, and cable entries. | IEC 60529. | Choose protection based on the installation environment; an IP code describes enclosure protection and does not by itself establish corrosion resistance. |
| Internal separation | Construction details for separation between busbars, functional units, and terminals, where required by the project. | IEC 61439-2; project specification. | Specify the required form of separation and access needs. Separation form should not be assumed from the product category alone. |
| North American product requirements | For projects in North America, confirm the assembly type, applicable product standard, certification or listing, and local installation requirements. | UL 891 for switchboards; UL 1558 for metal-enclosed low-voltage power circuit breaker switchgear; NFPA 70 (NEC) for electrical installations. | The applicable standard depends on the equipment type and project jurisdiction. NFPA 70 is an installation code, not a product certification standard. |
| Documentation and lifecycle support | General arrangement drawings, single-line diagrams, wiring documentation, component schedules, maintenance instructions, and spare-parts availability. | Project contract, applicable standards, and local regulatory requirements. | Confirm documentation language, revision control, commissioning support, and service coverage before purchase. |